Add to Cart
XLPE Insulated High Voltage Power Cables Single Core Longitudinally Watertight
Application:
To be laid directly in ground, outdoors, in water,indoors and in cable ducts.
Construction:
Standards:
Technical data:
Test voltage | 6 / 10 kV | [kV] | 21 / 5 min. |
12 / 20 kV | [kV] | 42 / 5 min. | |
18 / 30 kV | [kV] | 63 / 5 min. | |
Temperature range | in motion | -5°C till +90°C | |
fixed | -20°C till +90°C | ||
Operating temperature | short circuit | °C | 250 |
Short circuit time | max. | [sec] | 5 |
Bending radius | min. | x diameter | 15 |
Flammability | standard | EN 60332-1-2 |
Number of cores and nominal cross section mm2 |
Aluminium figure kg/km |
Copper figure kg/km |
Overall diameter appr. mm |
Overall diameter max. value appr. mm |
Weight appr. kg/km |
Current carrying capacity ground A |
Current carrying capacity air A |
|||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
1 x 50 RM/16 | 147,0 | 190 | 28 | 33 | 820,0 | 172 | 185 | |||||||
1 x 70 RM/16 | 206,0 | 190 | 30 | 35 | 930,0 | 210 | 231 | |||||||
1 x 95 RM/16 | 279,0 | 190 | 31 | 36 | 1.050,0 | 251 | 280 | |||||||
1 x 120 RM/16 | 353,0 | 190 | 33 | 38 | 1.150,0 | 285 | 323 | |||||||
1 x 150 RM/25 | 441,0 | 295 | 34 | 39 | 1.350,0 | 319 | 366 | |||||||
1 x 185 RM/25 | 544,0 | 295 | 36 | 41 | 1.500,0 | 361 | 420 | |||||||
1 x 240 RM/25 | 706,0 | 295 | 39 | 44 | 1.750,0 | 417 | 496 | |||||||
1 x 300 RM/25 | 882,0 | 295 | 41 | 46 | 2.000,0 | 471 | 569 | |||||||
1 x 400 RM/35 | 1.176,0 | 410 | 44 | 49 | 2.350,0 | 535 | 660 | |||||||
1 x 500 RM/35 | 1.470,0 | 410 | 47 | 52 | 2.800,0 | 609 | 766 |