High Voltage Overhead Power Lines Overhead Electrical Wire DIN 48201 BS 215
APPLICATION
AAAC is used as a bare overhead conductor for power transmission and distribution lines, on aerial circuits that require a larger mechanical resistance than AAC, and a better corrosion resistance than ACSR. The sag characteristics and the strength-to-weight ratio of AAAC is better than both AAC / ACSR.
CONSTRUCTION
Conductor
Aluminium alloy conductor Type AL2 to AL7 as per EN 50183 to BS 215
CABLE STANDARDS
ASTM - B 399 Metric Units, ASTM - B 231, TS IEC 1089, DIN 48201, BS 215, UNE 21.018
The electrical and dimensional properties of this product are measured by the Technical and Quality Assurance department at the Cables laboratory. Cable performance in respect of conductor resistance, construction quality (workmanship), dimensional consistency, and other parameters are verified to published standards and approved product drawings. Conformance to RoHS (Restriction of the use of Hazardous Substances) is determined and confirmed.
DIMENSIONS
ASTM Sizes
CODE |
SIZE KCM |
STRANDING |
DIAMETER inches |
NOMINAL CROSS SECTIONAL AREA (sq ins) |
WEIGHT lbs/1000ft |
RATED STRENGTH (lbs) |
RESISTANCE ohms/1000ft |
CURRENT RATING Amps |
SIZE |
ACSR WITH EQUIV.DIAM. STRANDING Alt/Stl |
||
Individual wires | Total |
DC 20ºC |
AC 75ºC |
|||||||||
AKRON | 30.58 | 7 | 0.0661 | 0.198 | 0.024 | 28.7 | 1110 | 0.659 | 0.785 | 107 | 6 | 61 |
ALTON | 48.69 | 7 | 0.0834 | 0.25 | 0.0382 | 45.7 | 1760 | 0.414 | 0.493 | 143 | 4 | 61 |
AMES | 77.47 | 7 | 0.1052 | 0.316 | 0.0608 | 72.7 | 2800 | 0.26 | 0.31 | 191 | 2 | 61 |
AZUSA | 123.3 | 7 | 0.1327 | 0.398 | 0.0968 | 115.7 | 4460 | 0.163 | 0.195 | 256 | 1/0 | 61 |
ANAHEIM | 155.4 | 7 | 0.149 | 0.447 | 0.1221 | 145.9 | 5390 | 0.13 | 0.154 | 296 | 2/0 | 61 |
AMHERST | 195.7 | 7 | 0.1672 | 0.502 | 0.1537 | 183.7 | 6790 | 0.103 | 0.1230 | 342 | 3/0 | 61 |
ALLIANCE | 246.9 | 7 | 0.1878 | 0.563 | 0.1939 | 231.8 | 8560 | 0.0816 | 0.0973 | 395 | 4/0 | 61 |
BUTTE | 312.8 | 19 | 0.1283 | 0.642 | 0.2456 | 293.6 | 11000 | 0.0644 | 0.0769 | 460 | 266.8 | 267 |
CANTON | 394.5 | 19 | 0.1441 | 0.721 | 0.3098 | 370.3 | 13300 | 0.0511 | 0.061 | 532 | 336.4 | 267 |
CAIRO | 465.4 | 19 | 0.1565 | 0.783 | 0.3655 | 436.9 | 15600 | 0.0433 | 0.0518 | 590 | 397.5 | 267 |
DARIEN | 559.5 | 19 | 0.1716 | 0.858 | 0.4394 | 525.2 | 18800 | 0.036 | 0.0431 | 663 | 477 | 2617 |
ELGIN | 652.4 | 19 | 0.1853 | 0.927 | 0.5124 | 612.4 | 21900 | 0.0309 | 0.0371 | 729 | 556.5 | 2617 |
FLINT | 740.8 | 37 | 0.1415 | 0.991 | 0.5818 | 695.5 | 24400 | 0.0272 | 0.0327 | 790 | 636 | 267 |
GREELY | 927.2 | 37 | 0.1583 | 1.108 | 0.7282 | 870.4 | 30500 | 0.0217 | 0.0263 | 908 | 795 | 267 |
Resistance is calculated using ASTM standard increments of stranding, and metal conductivity of 52.5% IACS. AC resistance at 60 Hz.
Current ratings are based on 75ºC conductor temperature, 250ºC ambient, 2 ft/s wind, 96/watts/sq.foot sun, 0.5 coefficients of emissivity and absorption.
ASTM Sizes
CONDUCTOR SIZE c mil |
AREA mm2 |
NO. AND DIAMETER OF WIRES | OVERALL DIAMETER OF CONDUCTOR | LINEAR WEIGHT |
RATED STRENGTH lb |
MAXIMUM DC RESISTANCE AT 20ºC ohms/km |
|||
inch | mm | inch | mm | kg/km | daN | ||||
66360 | 33.62 | 7 x 0.0974 | 7 x 2.47 | 0.291 | 7.41 | 93 | 1068 | 24 | 0.9942 |
105600 | 53.5 | 7 x 0.1228 | 7 x 3.12 | 0.368 | 9.36 | 148 | 1697 | 3815 | 0.6256 |
133100 | 67.44 | 7 x 0.1379 | 7 x 3.5 | 0.413 | 10.5 | 187 | 2052 | 4612 | 0.4959 |
167800 | 85.02 | 7 x 0.1548 | 7 x 3.93 | 0.464 | 11.8 | 235 | 2586 | 581 | 0.3936 |
211600 | 107.21 | 7 x 0.1739 | 7 x 4.42 | 0.522 | 13.26 | 296 | 3263 | 7332 | 0.3119 |
400000 | 202.68 | 19 x 0.1451 | 19 x 3.68 | 0.724 | 18.4 | 560 | 5974 | 13426 | 0.165 |
450000 | 228 | 19 x 0.1539 | 19 x 3.91 | 0.769 | 19.55 | 630 | 6719 | 151 | 0.1487 |
500000 | 253.35 | 19 x 0.1622 | 19 x 4.12 | 0.811 | 20.6 | 700 | 4764 | 16774 | 0.1321 |
550000 | 278.68 | 37 x 0.1219 | 37 x 3.1 | 0.854 | 21.7 | 769 | 8380 | 18835 | 0.1202 |
600000 | 304 | 37 x 0.1273 | 37 x 3.23 | 0.89 | 22.6 | 839 | 9138 | 20535 | 0.1102 |
650000 | 329.35 | 37 x 0.1325 | 37 x 3.36 | 0.926 | 23.52 | 910 | 9494 | 21336 | 0.1016 |
700000 | 354.7 | 37 x 0.1375 | 37 x 3.49 | 0.962 | 24.43 | 978 | 10220 | 22967 | 0.0944 |
750000 | 380 | 37 x 0.1424 | 37 x 3.61 | 0.995 | 25.27 | 1050 | 10940 | 2463 | 0.088 |
800000 | 405.36 | 37 x 0.147 | 37 x 3.73 | 1.02 | 26.1 | 1118 | 11680 | 26248 | 0.0826 |
900000 | 456 | 37 x 0.156 | 37 x 3.96 | 1.09 | 27.72 | 1260 | 13150 | 29551 | 0.0733 |
1000000 | 506.7 | 37 x 0.1644 | 37 x 4.17 | 1.15 | 29.2 | 1400 | 14610 | 32832 | 0.066 |
ASTM Sizes Metric Units
CODE |
SIZE KCM |
NOMINAL SIZE mm2 |
STRANDING |
DIAMETER inches |
WEIGHT11 lbs/1000ft |
RATED STRENGTH2 kg |
RESISTANCE3 ohms/1000ft |
CURRENT RATING4 Amps |
SIZE mm2 |
ACSR WITH EQUIV.DIAM. STRANDING alt/stl |
||
Individual Wires | Total |
DC at 20ºC |
AC at 75ºC |
|||||||||
AKRON | 30.58 | 15.5 | 7 | 1.679 | 5.04 | 42.7 | 503 | 2.16 | 2.57 | 107 | 13.3 | 6/1 |
ALTON | 48.69 | 24.67 | 7 | 2.118 | 6.36 | 68 | 798 | 1.36 | 1.62 | 143 | 21.15 | 6/1 |
AMES | 77.47 | 39.25 | 7 | 2.672 | 8.02 | 108.2 | 1270 | 0.853 | 1.02 | 191 | 33.63 | 6/1 |
AZUSA | 123.3 | 62.48 | 7 | 3.371 | 10.11 | 172.2 | 2023 | 0.536 | 0.639 | 256 | 53.31 | 6/1 |
ANAHEIM | 155.4 | 78.74 | 7 | 3.785 | 11.35 | 217.1 | 2445 | 0.425 | 0.509 | 296 | 67.44 | 6/1 |
AMHERST | 195.7 | 99.16 | 7 | 4.247 | 12.74 | 273.3 | 3080 | 0.338 | 0.403 | 342 | 85.03 | 6/1 |
ALLIANCE | 246.9 | 125.1 | 7 | 4.77 | 14.31 | 344.9 | 3883 | 0.268 | 0.319 | 395 | 107.22 | 6/1 |
BUTTE | 312.8 | 158.5 | 19 | 3.259 | 16.29 | 436.9 | 4989 | 0.211 | 0.252 | 460 | 135.19 | 26/7 |
CANTON | 394.5 | 199.9 | 19 | 3.66 | 18.3 | 551.1 | 6033 | 0.168 | 0.2 | 532 | 170.46 | 26/7 |
CAIRO | 465.4 | 235.8 | 19 | 3.975 | 19.88 | 650 | 7076 | 0.142 | 0.17 | 590 | 201.42 | 26/7 |
DARIEN | 559.5 | 283.5 | 19 | 4.359 | 21.79 | 781.5 | 8527 | 0.118 | 0.142 | 663 | 241.7 | 26/7 |
ELGIN | 652.4 | 330.6 | 19 | 4.707 | 23.53 | 911.3 | 9934 | 0.101 | 0.122 | 729 | 281.98 | 26/7 |
FLINT | 740.8 | 375.4 | 37 | 3.594 | 25.16 | 1035 | 11068 | 0.0892 | 0.107 | 790 | 322.27 | 26/7 |
GREELY | 927.2 | 469.8 | 37 | 4.021 | 28.15 | 1295 | 13834 | 0.0713 | 0.0863 | 908 | 402.83 | 26/7 |
Weights are calculated using ASTM standard increments of stranding.
Rated strengths are calculated by ASTM methods and converted to metric units after rounding.
Resistance is calculated using ASTM standard increments of stranding, and metal conductivity of 52.5% IACS, AC resistance at 60 Hz.
Current ratings are based on 751ºC conductor temperature, 250ºC ambient, 0.61 m/s wind, 1033 watts/sq. meter sun, 0.5 coefficients of emissivity and absorption.