Add to Cart
318A / BS 6004 Arctic Grade Wire Stranded Conductor Blue Brown Green Yellow
APPLICATION
Arctic grade PVC cords manufactured to BS 6004 are designed to withstand severe external temperatures and will remain flexible at temperatures down to -40°C. Making them particularly suitable for outdoor applications and for use where flexibility is required at sub zero temperatures. At normal temperatures the cable is very flexible, offering some of the characteristics usually found in elastomeric cables.
CONSTRUCTION
Conductor
Class 5 flexible copper conductor according to BS EN 60228 (previously BS 6360)
Insulation
Arctic grade PVC (Polyvinyl Chloride) Type TI4 according to BS EN 50363
Sheath
Arctic grade PVC (Polyvinyl Chloride) Type 10 according to BS 7655
CABLE STANDARDS
BS 6004 (previously BS 7919 Table 44), BS EN/IEC 60332-1-2
The electrical and dimensional properties of this product are measured by the Technical and Quality Assurance department at the Sunwin Cables laboratory.
Cable performance in respect of conductor resistance, construction quality (workmanship), dimensional consistency, and other parameters are verified to published standardsand approved product drawings. Conformance to RoHS (Restriction of the use ofHazardous Substances) is determined and confirmed.
CHARACTERISTICS
Voltage Rating (Uo/U) 300/500V
Temperature Rating
Fixed: -40°C to +60°C
Minimum Bending Radius
Fixed: 6 x overall diameter
Core Identification
Sheath Colour
Blue Yellow
DIMENSIONS
Sunwin PART NO. | NO. OF CORES |
NOMINAL CROSS SECTIONAL AREA mm² |
NOMINAL THICKNESS OF INSULATION mm |
NOMINAL THICKNESS OF SHEATH mm |
NOMINAL OVERALL DIAMETER mm |
NOMINAL WEIGHT kg/km |
A5A2075*1R | 2 | 0.75 | 0.6 | 0.8 | 6.2 | 55 |
A5A2010*1R | 2 | 1 | 0.6 | 0.8 | 6.4 | 61 |
A5A201*1R | 2 | 1.5 | 0.7 | 0.8 | 7.4 | 83 |
A5A202*1R | 2 | 2.5 | 0.8 | 1 | 9.2 | 130 |
A5A204*1R | 2 | 4 | 0.8 | 1.1 | 10.4 | 176 |
A5A206*1R | 2 | 6 | 0.8 | 1.2 | 11.3 | 299 |
A5A3010*1R | 3 | 1 | 0.6 | 0.8 | 6.8 | 73 |
A5A301*1R | 3 | 1.5 | 0.7 | 0.9 | 8.1 | 105 |
A5A302*1R | 3 | 2.5 | 0.8 | 1.1 | 10 | 163 |
A5A304*1R | 3 | 4 | 0.8 | 1.2 | 11.3 | 224 |
A5A306*1R | 3 | 6.0 | 0.8 | 1.2 | 12.7 | 299 |
* Sunwin Part No. shown above designate the sheath colour (*). For each colour substitute * for a colour code as listed below. e.g. A5A2075B1R = 0.75mm2 Blue
Colour Codes
COLOUR | Blue | Yellow |
CODE | B | Y |
CONDUCTORS
Class 5 Flexible Copper Conductors for Single Core and Multi-Core Cables
NOMINAL CROSS SECTIONAL AREA mm² |
MAXIMUM DIAMETER OF WIRES IN CONDUCTOR mm |
MAXIMUM RESISTANCE OF CONDUCTOR AT 20ºC |
Plain Wires ohms/km |
||
0.75 | 0.21 | 26 |
1 | 0.21 | 19.5 |
1.5 | 0.26 | 13.3 |
2.5 | 0.26 | 7.98 |
4 0.31 | 4.95 | |
6 | 031 | 3.30 |
ELECTRICAL CHARACTERISTICS
Current Carrying Capacity
NOMINAL CROSS SECTIONAL AREA mm² |
CURRENT CARRYING CAPACITY AT 30ºC | |
Single-Phase AC Amps |
Three-Phase AC Amps |
|
0.75 | 6 | 6 |
1 | 10 | 10 |
1.5 | 16 | 16 |
2.5 | 25 | 20 |
4 | 32 | 25 |
6 | 48 | 40 |
Voltage Drop
NOMINAL CROSS SECTIONAL AREA mm² |
DC OR SINGLE-PHASE AC mV/A/m |
THREE-PHASE AC mV/A/m |
0.75 | 62 | 54 |
1 | 46 | 40 |
1.5 | 32 | 27 |
2.5 | 19 | 16 |
4 | 12 | 10 |
6 | 8 | 7 |
Conductor operating temperature: 60ºC
The above table is in accordance with Table 4F3B of the 17th Edition of IEE Wiring Regulations.
DE-RATING FACTORS
60ºC Thermoplastic or Thermosetting Insulated Cords
AMBIENT TEMPERATURE | 35ºC | 40ºC | 45ºC | 50ºC | 55ºC |
DE-RATING FACTOR | 0.91 | 0.82 | 0.71 | 0.58 | 0.41 |
The above table is in accordance with Table 4F3A of the 17th Edition of IEE Wiring Regulations.
The information contained within this datasheet is for guidance only and is subject to change without notice or liability. All the information is provided in good faith and is believed to be correct at the time of publication. When selecting cable accessories, please note that actual cable dimensions may vary due to manufacturing tolerances.