PVC Type 6 Insulated Electrical Wire Domestic Wiring Cable BS 6004 624 Y
APPLICATION
Domestic wiring cable. Can be installed in fixed installations in dry or damp premises clipped to surface, on trays or in free air where the risk of mechanical damage would not be an issue. Suitable for laying in conduit or trunking where mechanical protection is required.
CONSTRUCTION
Conductor
Copper conductor according to BS EN 60228 (previously BS 6360)
1mm² to 2.5mm²: Class 1 solid conductor 4mm² to 16mm²: Class 2 stranded conductor
Circuit Protection Conductor (Earth)
1mm² to 2.5mm²: Class 1 solid copper conductor 4mm² to 16mm²: Class 2 stranded copper conductor
Insulation
PVC (Polyvinyl Chloride) Type TI1 according to BS EN 50363
Sheath
PVC (Polyvinyl Chloride) Type 6 according to BS 7655
CABLE STANDARDS
BS 6004 Table 4
The electrical and dimensional properties of this product are measured by the Technical and Quality Assurance department at the Sunwin Cables laboratory.
Cable performance in respect of conductor resistance, construction quality (workmanship),dimensional consistency, and other parameters are verified to published standardsand approved product drawings. Conformance to RoHS (Restriction of the use ofHazardous Substances) is determined and confirmed
CHARACTERISTICS
Voltage Rating (Uo/U) 300/500V
-5°C to +70°C
Short Circuit : +160°C
Minimum Bending Radius
Fixed: 6 x overall diameter
Core Identification
Brown Blue
Sheath Colour
Grey
DIMENSIONS
Sunwin PART NO. | NO. OF CORES |
NOMINAL CROSS SECTIONAL AREA mm² |
CONDUCTOR CLASS |
CROSS SECTIONAL AREA OF CIRCUIT PROTECTIVE CONDUCTOR mm² |
NOMINAL THICKNESS OF INSULATION mm |
NOMINAL THICKNESS OF SHEATH mm |
NOMINAL OVERALL DIMENSIONS mm |
NOMINAL WEIGHT kg/km |
A9A2010GR | 2 | 1 | 1 | 1 | 0.6 | 0.9 | 4.35 x 7.95 | 68 |
A9A2015GR | 2 | 1.5 | 1 | 1 | 0.7 | 0.9 | 4.85 x 8.9 | 87 |
A9A2025GR | 2 | 2.5 | 1 | 1.5 | 0.8 | 1 | 5.65 x 10.65 | 120 |
A9A2040GR | 2 | 4 | 2 | 1.5 | 0.8 | 1 | 6.3 x 11.95 | 172 |
A9A2060GR | 2 | 6 | 2 | 2.5 | 0.8 | 1.1 | 7.1 x 13.7 | 235 |
A9A210GR | 2 | 10 | 2 | 4* | 1 | 1.2 | 8.7 x 17.25 | 373 |
A9A216GR | 2 | 16 | 2 | 6* | 1 | 1.3 | 9.85 x 20 | 530 |
A9A3010GR | 3 | 1 | 1 | 1 | 0,6 | 0.9 | 4.35 x 9.8 | 91 |
A9A3010GR | 3 | 1.5 | 1 | 1 | 0.7 | 0.9 | 4.85 x 11.2 | 115 |
*Class 2 conductors only
CONDUCTORS
Class 1 Solid Conductors for Single Core and Multi-Core Cables
NOMINAL CROSS SECTIONAL AREA mm² |
MAXIMUM RESISTANCE OF CONDUCTOR AT 20ºC |
Plain Wires ohms/km |
|
1 | 18.1 |
1.5 | 12.1 |
2.5 | 7.41 |
The above table is in accordance with BS EN 60228 (previously BS 6360)
Class 2 Stranded Conductors for Single Core and Multi-Core Cables
NOMINAL CROSS SECTIONAL AREA mm² |
MINIMUM NO. OF WIRES IN CONDUCTOR | MAXIMUM RESISTANCE OF CONDUCTOR AT 20ºC |
Circular |
Annealed Copper Conductor | |
Plain Wires ohms/km |
||
4 | 7 | 4.61 |
6 | 7 | 3.08 |
10 | 7 | 1.83 |
16 | 7 | 1.15 |
The above table is in accordance with BS EN 60228 (previously BS 6360)
ELECTRICAL CHARACTERISTICS
Current Carrying Capacity and Voltage Drop
NOMINAL CROSS SECTIONAL AREA mm² |
REFERENCE METHOD A* (IN CONDUIT IN WALL) Amps |
REFERENCE METHOD C* (CLIPPED DIRECT) Amps |
VOLTAGE DROP mv/A/m |
1 | 11.5 | 16 | 44 |
1.5 | 14.5 | 20 | 29 |
2.5 | 20 | 27 | 18 |
4 | 26 | 37 | 11 |
6 | 32 | 47 | 7.3 |
10 | 44 | 64 | 4.4 |
16 | 57 | 85 | 2.8 |
The above table is in accordance with 4D5 of the 17th Edition of IEE Wiring Regulations. Note
A* For full installation method refer to Table 4A2 Installation Method 2 but for flat twin and earth cable of the 17th Edition of IEE Wiring Regulations. C* For full installation method refer to Table 4A2 Installation Method 20 but for flat twin and earth cable of the 17th Edition of IEE Wiring Regulations.
The information contained within this datasheet is for guidance only and is subject to change without notice or liability. All the information is provided in good faith and is believed to be correct at the time of publication. When selecting cable accessories, please note that actual cable dimensions may vary due to manufacturing tolerances.