Flexible Copper Insulated Electrical Wire H05Z K H07Z K BS EN 50525-3-41 Cable

Ask Latest Price
Video Channel
CHARACTERISTICS :Voltage Rating (Uo/U)
Conductor :Flexible Copper (Class 5)
Insulation :LSZH (Low Smoke Zero Halogen) Type
Temperature Rating :-25°C to +90°C
Sheath Colour :Red Black Blue Light Blue Dark Blue,etc.
CABLE STANDARDS :BS EN/IEC 50267-2-1, BS EN/IEC 60754
Place of Origin :Guangzhou, China
Brand Name :SUNWIN
Certification :ISO9001, ISO14001, OHSAS18001
MOQ :Negotiable
Price :Negotiable
Packaging Details :100 m / tied, or customized
Delivery Time :10 day
Payment Terms :30% deposit, the balance is settled on the delivery date
Supply Ability :100,000 m / month
more
Contact Now

Add to Cart

Find Similar Videos
View Product Description

Flexible Copper Insulated Electrical Wire H05Z K H07Z K BS EN 50525-3-41 Cable

APPLICATION

LSZH panel wiring for appliances with maximum operating temperatures of 90°C, and generally in areas (such as public and government buildings) where smoke and toxic fumes may cause a threat to life and equipment. The cables produce no corrosive gases when burnt which is particularly important where electronic equipment is installed.

CONSTRUCTION

Conductor

Class 5 flexible copper conductor according to BS EN 60228 (previously BS 6360)

Insulation

LSZH (Low Smoke Zero Halogen) Type EI5 thermosetting insulation according to BS EN 50363

CABLE STANDARDS

BS EN 50525-3-41 (previously BS 7211 Table 3 and 4b CENELEC HD22.9), BS EN/IEC 60332-1-2,

BS EN/IEC 50267-2-1, BS EN/IEC 60754

The electrical and dimensional properties of this product are measured by the Technical and Quality Assurance department at the Sunwin Cables laboratory.

Cable performance in respect of conductor resistance, construction quality (workmanship),dimensional consistency, and other parameters are verified to published standardsand approved product drawings. Conformance to RoHS (Restriction of the use ofHazardous Substances) is determined and confirmed.

CHARACTERISTICS

Voltage Rating (Uo/U)

H05Z-K - 0.5mm2 to 1mm2: 300/500V H07Z-K - 1.5mm2 to 240mm2: 450/750V

Temperature Rating

-25°C to +90°C

Minimum Bending Radius

Up to 35mm2: 4 x overall diameter 50mm2 and above: 6 x overall diameter

Insulation Colour

Red Black Blue Orange White Yellow Green/Yellow Grey Brown Violet Pink

DIMENSIONS

H05Z-K

Sunwin PART NO.

NOMINAL CROSS SECTIONAL AREA

mm²

THICKNESS OF INSULATION

mm

NOMINAL OVERALL DIAMETER

MINIMUM RESISTANCE OF INSULATION AT 90°C

Mohms/km

NOMINAL WEIGHT

kg/km

Lower Limit

mm

Upper Limit

mm

A2Z*0050 0.5 0.6 1.9 2.4 0.015 8.7
A2Z*0075 0.75 0.6 2.2 2.8 0.011 11.3
A2Z*0010 1 0.6 2.4 2.9 0.01 13.9

H07Z-K

Sunwin PART NO.

NOMINAL CROSS SECTIONAL AREA

mm²

NOMINAL THICKNESS OF INSULATION

mm

NOMINAL OVERALL DIAMETER

MINIMUM RESISTANCE OF INSULATION AT 900C

Mohms/km

NOMINAL WEIGHT

kg/km

Lower limit

mm

Upper limit

mm

A2Z*0015 1.5 0.7 2.8 3.5 0.010 19.3
A2Z*0025 2.5 0.8 3.4 4.3 0.009 30.9
A2Z*0040 4 0.8 3.9 4.9 0.007 44.9
A2Z*0060 6 0.8 4.4 5.5 0.006 64.2
A2Z*010 10 1 5.7 7.1 0.0056 108.2
A2Z*016 16 1 6.7 8.4 0.0046 163.4
A2Z*025 25 1.2 8.4 10.6 0.0044 248.1
A2Z*035 35 1.2 9.7 12.1 0.0038 340.6
A2Z*050 50 1.4 11.5 14.4 0.0037 484.2
A2Z*070 70 1.4 13.2 16.6 0.0032 671
A2Z*095 95 1.6 15.1 18.8 0.0032 895.8
A2Z*120 120 1.6 16.7 20.9 0.0029 1111.1
A2Z*150 150 1.8 18.6 23.3 0.0029 1389.2
A2Z*185 185 2 20.6 25.8 0.0029 1724.1
A2Z*240 240 2.2 23.5 29.4 0.0028 2225.4

*Sunwin Part No. shown above designate the sheath colour (*). For each colour substitute * for a colour code as listed below. e.g. A2ZRD0015 = 1.5mm2 Red

Colour Codes

COLOUR Black Blue Grey Green/ Yellow Orange Red Pink Yellow Violet Brown White
CODE BK BL GR GY OR RD PK YW VI BR WH

CONDUCTORS

Class 5 Flexible Copper Conductors for Single Core and Multi-Core Cables

NOMINAL CROSS SECTIONAL AREA

mm²

MAXIMUM DIAMETER OF WIRES IN CONDUCTOR

mm

MAXIMUM RESISTANCE OF CONDUCTOR AT 20ºC

Plain Wires

ohms/km

0.5 0.21 39
0.75 0.21 26
1 0.21 19.5
1.5 0.26 13.3
2.5 0.26 7.98
4 0.31 4.95
6 0.31 3.3
10 0.41 1.91
16 0.41 1.21
25 0.41 0.78
35 0.41 0.554
50 0.41 0.386
70 0.51 0.272
95 0.51 0.206
120 0.51 0.161
150 0.51 0.129
185 0.51 0.106
240 0.51 0.0801

The above table is in accordance with BS EN 60228 (previously BS 6360)

ELECTRICAL CHARACTERISTICS

Current Carrying Capacity

NOMINAL CROSS SECTIONAL AREA

mm²

REFERENCE METHOD A (ENCLOSED IN CONDUIT IN THERMALLY INSULATING WALL ETC)

Amps

REFERENCE METHOD B (ENCLOSED IN CONDUIT ON A WALL OR IN A TRUNKING ETC)

Amps

REFERENCE METHOD C (CLIPPED DIRECT)

Amps

REFERENCE METHOD F

(IN FREE AIR OR ON A PERFORATED CABLE TRAY ETC HORIZONTAL OR VERTICAL ETC) TOUCHING

Amps

REFERENCE METHOD G (IN FREE AIR) SPACED BY ONE CABLE DIAMETER

Amps

2 Cables Single-Phase AC or DC or

3 Cables Three-Phase AC flat

2 Cables Single-Phase AC or DC

3 or 4 Cables Three-Phase AC

2 Cables Single-Phase AC or DC

3 or 4 Cables Three-Phase AC

2 Cables Single-Phase AC or DC flat or touching

3 or 4 Cables Three-Phase AC flat and touching or trefoil

2 Cables Single-Phase AC or DC

flat

3 Cables Three-Phase AC

flat

3 Cables Three-Phase AC

trefoil

Horizontal

Vertical

1 14 13 17 15 19 17.5 - - - - -
1.5 19 17 23 20 25 23 - - - - -
2.5 26 23 31 28 34 31 - - - - -
4 35 31 42 37 46 41 - - - - -
6 45 40 54 48 59 54 - - - - -
10 61 54 75 66 81 74 - - - - -
16 81 73 100 88 109 99 - - - - -
25 106 95 133 117 143 130 161 141 135 182 161
35 131 117 164 144 176 161 200 176 169 226 201
50 158 141 198 175 228 209 242 216 207 275 246
70 200 179 253 222 293 268 310 279 268 353 318
95 241 216 306 269 355 326 377 342 328 430 389
120 278 249 354 312 413 379 437 400 383 500 454
150 318 285 393 342 476 436 504 464 444 577 527
185 362 324 449 384 545 500 575 533 510 661 605
240 424 380 528 450 644 590 679 634 607 781 719

Ambient temperature: 30ºC

Conductor operating temperature: 90ºC

  1. Where a conductor operates at a temperature exceeding 70ºC it must be ascertained that the equipment connected to the conductor is suitable for the conductor operating temperature (see also Regulation 512.1.2).

  1. Where cables in this table are connected to equipment or accessories designed to operate at a temperature not exceeding 70ºC, the current ratings given in the equivalent table for 70ºC thermoplastic insulated cables (Table 4D1A) must be used (see Regulation 523.1).

The above table is in accordance with Table 4E1A of the 17th Edition of IEE Wiring Regulations.

Voltage Drop

NOMINAL CROSS SECTIONAL AREA

mm²

2 CABLES DC

mV/A/m

2 CABLES SINGLE-PHASE AC

mV/A/m

3 OR 4 CABLES THREE-PHASE AC

mV/A/m

Reference Methods A and B

(enclosed in conduit or trunking)

Reference Methods C, F and G (clipped direct, on tray or in free air)

Reference Methods A and B

(enclosed in conduit

or trunking)

Reference Methods C, F and G

(clipped direct, on tray or in free air)

Cable Touching

Cable Spaced

Cable

Touching Trefoil

Cable

Touching Flat

Cable

Spaced* Flat

1 46 46 46 46 40 40 40 40
1.5 31 31 31 31 27 27 27 27
2.5 19 19 19 19 16 16 16 16
4 12 12 12 12 10 10 10 10
6 7.9 7.9 7.9 7.9 6.8 6.8 6.8 6.8
10 4.7 4.7 4.7 4.7 4 4 4 4
16 2.9 2.9 2.9 2.9 2.5 2.5 2.5 2.5
r x z r x z r x z r x z r x z r x z r x z
25 1.85 1.850 0.310 1.900 1.850 0.190 1.85 1.850 0.280 1.850 1.600 0.270 1.650 1.600 0.165 1.600 1.600 0.190 1.600 1.600 0.270 1.650
35 1.35 1.350 0.290 1.350 1.350 0.180 1.35 1.350 0.270 1.350 1.150 0.250 1.150 1.150 0.155 1.150 1.150 0.180 1.150 1.150 0.260 1.200
50 0.99 1.000 0.290 1.050 0.990 0.180 1.000 0.990 0.270 1.000 0.870 0.250 0.900 0.860 0.155 0.870 0.860 0.180 0.870 0.860 0.260 0.890
70 0.68 0.700 0.280 0.750 0.680 0.175 0.710 0.680 0.260 0.730 0.600 0.240 0.650 0.590 0.150 0.610 0.590 0.175 0.620 0.590 0.250 0.650
95 0.49 0.510 0.270 0.580 0.490 0.170 0.520 0.490 0.260 0.560 0.440 0.230 0.500 0.430 0.145 0.450 0.430 0.170 0.460 0.430 0.250 0.490
120 0.39 0.410 0.260 0.480 0.390 0.165 0.430 0.390 0.250 0.470 0.350 0.230 0.420 0.340 0.140 0.370 0.340 0.165 0.380 0.340 0.240 0.420

Conductor operating temperature: 90ºC

r = Resistive Component x = Reactive Component z = Impedance Value

* Spacings larger than one cable diameter will result in a larger voltage drop.

The above table is in accordance with Table 4E1B of the 17th Edition of IEE Wiring Regulations.

For cables having conductors of 16mm2 or less cross-sectional area their inductances can be ignored and (mV/A/m)r values only are tabulated. For cables having conductors greater than 16mm2, cross-sectional area the impedance values are given as (mV/A/m)z, together with the resistive component (mV/A/m)r and the reactive component (mV/A/m)x.

The above paragraph is extracted from Appendix 4 of the 17th Edition of IEE Wiring Regulations.

DE-RATING FACTORS

AMBIENT TEMPERATURE 25ºC 30ºC 35ºC 40ºC 45ºC 50ºC 55ºC 60ºC 65ºC 70ºC 85ºC 90ºC 95ºC
DE-RATING FACTOR 1.02 1.00 0.96 0.91 0.87 0.82 0.76 0.71 0.65 0.58 - - -

The information contained within this datasheet is for guidance only and is subject to change without notice or liability. All the information is provided in good faith and is believed to be correct at the time of publication. When selecting cable accessories, please note that actual cable dimensions may vary due to manufacturing tolerances.