309-Y / H05V2V2-F BS EN 50525-2-11 Flexible Cable
APPLICATION
For internal wiring or supply cords to electrical apparatus, particularly for use in high temperature zones such as lighting applications. Not suitable for outdoor use.
CONSTRUCTION
Conductor
Class 5 flexible copper conductor according to BS EN 60228 (previously BS 6360)
Insulation
PVC (Polyvinyl Chloride) Type TI3 according to BS EN 50363
Sheath
PVC (Polyvinyl Chloride) Type TM3 according to BS EN 50363
CABLE STANDARDS
BS EN 50525-2-11 (previously BS 6500, BS 7919 table 41),
BS EN/IEC 60332-1-2
The electrical and dimensional properties of this product are measured by the Technical and Quality Assurance department at the Sunwin Cables laboratory.
Cable performance in respect of conductor resistance, construction quality (workmanship),dimensional consistency, and other parameters are verified to published standardsand approved product drawings. Conformance to RoHS (Restriction of the use ofHazardous Substances) is determined and confirmed.
CHARACTERISTICS
Voltage Rating (Uo/U) 300/500V
Temperature Rating
Flexed: 0°C to +90°C
Minimum Bending Radius Fixed: 6 x overall diameter Flexed: 10 x overall diameter
Core Identification
Sheath Colour
White
DIMENSIONS
Sunwin PART NO. | NO. OF CORES |
NOMINAL CROSS SECTIONAL AREA mm² |
NOMINAL THICKNESS OF INSULATION mm |
NOMINAL THICKNESS OF SHEATH mm |
NOMINAL OVERALL DIAMETER mm |
NOMINAL WEIGHT kg/km |
A5Y020075HRWH | 2 | 0.75 | 0.6 | 0.8 | 6.3 | 63 |
A5Y030075HRWH | 3 | 0.75 | 0.6 | 0.8 | 6.7 | 74 |
A5Y03010HRWH | 3 | 1 | 0.6 | 0.8 | 7 | 86 |
A5Y03015HRWH | 3 | 1.5 | 0.7 | 0.9 | 8.1 | 115 |
A5Y03025HRWH | 3 | 2.5 | 0.8 | 1 | 9.7 | 170 |
A5Y040075HRWH | 4 | 0.75 | 0.6 | 0.8 | 7.3 | 78 |
A5Y04010HRWH | 4 | 1 | 0.6 | 0.9 | 7.9 | 110 |
A5Y04015HRWH | 4 | 1.5 | 0.7 | 1 | 9 | 140 |
A5Y04025HRWH | 4 | 2.5 | 0.8 | 1.1 | 10.8 | 210 |
A5Y050075HRWH | 5 | 0.75 | 0.6 | 0.9 | 8.1 | 105 |
CONDUCTORS
Class 5 Flexible Copper Conductors for Single Core and Multi-Core Cables
NOMINAL CROSS SECTIONAL AREA mm² |
MAXIMUM DIAMETER OF WIRES IN CONDUCTOR mm |
MAXIMUM RESISTANCE OF CONDUCTOR AT 20ºC | |
Plain Wires ohms/km |
Metal-Coated Wires ohms/km |
||
0.75 | 0.21 | 26 | 26.7 |
1 | 0.21 | 19.5 | 20 |
1.5 | 0.26 | 13.3 | 13.7 |
2.5 | 0.26 | 7.98 | 8.21 |
The above table is in accordance with BS EN 60228 (previously BS 6360)
ELECTRICAL CHARACTERISTICS
Current Carrying Capacity and Mass Supportable
NOMINAL CROSS SECTIONAL AREA mm2 |
CURRENT CARRYING CAPACITY |
MAXIMUM MASS SUPPORTABLE BY TWIN FLEXIBLE CORD (See Regulations 522.7.2 and 559.6.1.5 of the 17th Edition of IEE Wiring Regulations) kg |
|
Single-Phase AC Amps |
Three-Phase AC Amps |
||
0.75 | 6 | 6 | 3 |
1 | 10 | 10 | 5 |
1.5 | 16 | 16 | 5 |
2.5 | 25 | 20 | 5 |
The above table is in accordance with Table 4F3A of the 17th Edition of IEE Wiring Regulations.
Voltage Drop
NOMINAL CROSS SECTIONAL AREA mm² |
DC OR SINGLE-PHASE AC mV/A/m |
THREE-PHASE AC mV/A/m |
0.75 | 62 | 54 |
1 | 46 | 40 |
1.5 | 32 | 27 |
2.5 | 19 | 16 |
Conductor operating temperature: 60ºC*
* The tabulated values above are for 60ºC thermoplastic or thermosetting insulated flexible cords. For other types of flexible cords they are to be multiplied by the following factors: for thermoplastic or thermoset insulation at 90ºC: 1.09, at 105ºC: 1.31
The above table is in accordance with Table 4F3B of the 17th Edition of IEE Wiring Regulations.
DE-RATING FACTORS
De-Rating factor for ambient temperature 60ºC thermoplastic or thermosetting insulated cords
AIR TEMPERATURE | 35ºC | 40ºC | 45ºC | 50ºC | 55ºC |
DE-RATING FACTOR | 0.91 | 0.82 | 0.71 | 0.58 | 0.41 |
The above table is in accordance with Table 4F3A of the 17th Edition of IEE Wiring Regulations.
The information contained within this datasheet is for guidance only and is subject to change without notice or liability. All the information is provided in good faith and is believed to be correct at the time of publication. When selecting cable accessories, please note that actual cable dimensions may vary due to manufacturing tolerances.