6491X / H07V-R / H07V-U / BS EN 50525-2-31 Cable

Ask Latest Price
Video Channel
Conductor H07V-U :Class 1 solid copper conductor to BS EN 60228 (previously BS 6360)
Conductor H07V-R :Class 2 stranded copper conductor to BS EN 60228 (previously BS 6360)
Insulation :PVC (Polyvinyl Chloride) Type TI1 according to BS EN 50363
CHARACTERISTICS :Voltage Rating (Uo/U) 450/750V
Temperature Rating :-15°C to +70°C
Insulation Colour :Red Black Blue Yellow White Green/Yellow Grey Brown
Place of Origin :Guangzhou, China
Brand Name :SUNWIN
Certification :ISO9001, ISO14001, OHSAS18001
MOQ :Negotiable
Price :Negotiable
Packaging Details :100 m / tied, or customized
Delivery Time :10 day
Payment Terms :30% deposit, the balance is settled on the delivery date
Supply Ability :100,000 m / month
more
Contact Now

Add to Cart

Find Similar Videos
View Product Description

6491X / H07V-R / H07V-U / BS EN 50525-2-31 Cable

APPLICATION

6491X Cable H07V-R/H07V-U is suitable for power and lighting circuits and building wiring. The cable is intended for use in semi-flush exposed conduits and embedded conduits as well as in closed installation ducts, and is ideal for the internal wiring of appliances.

CONSTRUCTION

Conductor

H07V-R: Class 2 stranded copper conductor to BS EN 60228 (previously BS 6360)

H07V-U: Class 1 solid copper conductor to BS EN 60228 (previously BS 6360)

Insulation

PVC (Polyvinyl Chloride) Type TI1 according to BS EN 50363

CABLE STANDARDS

BS EN 50525-2-31 (previously BS 6004) BASEC approved, BS EN/IEC 60332-1-2

The electrical and dimensional properties of this product are measured by the Technical and Quality Assurance department at the Sunwin Cables laboratory.

Cable performance in respect of conductor resistance, construction quality (workmanship),dimensional consistency, and other parameters are verified to published standardsand approved product drawings. Conformance to RoHS (Restriction of the use ofHazardous Substances) is determined and confirmed.

CHARACTERISTICS

Voltage Rating (Uo/U) 450/750V

Temperature Rating

-15°C to +70°C

Minimum Bending Radius

Up to 10mm²: 3 x overall diameter 10mm² to 25mm²: 4 x overall diameter Above 25mm²: 5 x overall diameter

Insulation Colour

Red Black Blue Yellow White Green/Yellow Grey Brown

DIMENSIONS

Sunwin PART NO.

NOMINAL CROSS SECTIONAL AREA

mm²

NOMINAL THICKNESS OF INSULATION

mm

NOMINAL OVERALL DIAMETER

mm

NOMINAL WEIGHT

kg/km

A2X*0015 1.5 0.7 2.9 22
A2X*0025 2.5 0.8 3.6 32
A2X*0040 4 0.8 4.1 50
A2X*0060 6 0.8 4.7 71
A2X*010 10 1 5.9 110
A2X*016 16 1 6.8 164
A2X*025 25 1.2 8.4 256
A2X*035 35 1.2 9.4 346
A2X*050 50 1.4 11 473
A2X*070 70 1.4 12.7 674
A2X*095 95 1.6 14.7 913
A2X*120 120 1.6 16.2 1150
A2X*150 150 1.8 18 1416
A2X*185 185 2 20 1749
A2X*240 240 2.2 23 2317
A2X*300 300 2.4 25.2 3049
A2X*400 400 2.6 28.4 3657
A2X*500 500 2.8 31.8 4700
A2X*630 630 2.8 38.1 5890

* Sunwin Part No. shown above designate the sheath colour (*). For each colour substitute * for a colour code as listed below. e.g. A2XRD0040 = 4mm2 Red

Colour Codes

COLOUR Black Blue Grey Green/Yellow Red Yellow Brown White
CODE BK BL GR GY RD YW BR WH

CONDUCTORS

Class 2 Stranded Conductors for Single Core and Multi-Core Cables

NOMINAL CROSS SECTIONAL AREA

mm²

MINIMUM NO. OF WIRES IN CONDUCTOR MAXIMUM RESISTANCE OF CONDUCTOR AT 20ºC
Circular Circular Compacted Shaped Annealed Copper Conductor
Cu Al Cu Al Cu Al

Plain Wires

ohms/km

1.5 7 - 6 - - - 12.1
2.5 7 - 6 - - - 7.41
4 7 - 6 - - - 4.61
6 7 - 6 - - - 3.08
10 7 7 6 6 - - 1.83
16 7 7 6 6 - - 1.15
25 7 7 6 6 6 6 0.727
35 7 7 6 6 6 6 0.524
50 19 19 6 6 6 6 0.387
70 19 19 12 12 12 12 0.268
95 19 19 15 15 15 15 0.193
120 37 37 18 15 18 15 0.153
150 37 37 18 15 18 15 0.124
185 37 37 30 30 30 30 0.0991
240 37 37 34 30 34 30 0.0754
300 61 61 34 30 34 30 0.0601
400 61 61 53 53 53 53 0.047
500 61 61 53 53 53 53 0.0366
630 91 91 53 53 53 53 0.0283

The above table is in accordance with BS EN 60228 (previously BS 6360)

ELECTRICAL CHARACTERISTICS

Current Carrying Capacity

NOMINAL CROSS REFERENCE METHOD A REFERENCE METHOD B REFERENCE METHOD C REFERENCE METHOD F
SECTIONAL AREA (ENCLOSED IN CONDUIT (ENCLOSED IN CONDUIT (CLIPPED DIRECT)

(IN FREE AIR OR ON A PERFORATED

CABLE TRAY ETC HORIZONTAL

mm² IN THERMALLY ON A WALL OR IN A Amps OR VERTICAL ETC)
INSULATING WALL ETC) TRUNKING ETC) Amps
Amps Amps

Touching

Spaced by one diameter

2 Cables Single-Phase AC or DC or

3 Cables Three-Phase AC flat

2 Cables 3 or 4 Cables
2 Cables 3 or 4 Cables 2 Cables 3 or 4 Cables

Single-

Phase

Three-

Phase

2 Cables 3 Cables 3 Cables

Single-

Phase

Three-

Phase

Single-

Phase

Three-

Phase

AC or DC flat AC flat and

Single-

Phase

Three-

Phase

Three-

Phase

Horizontal Vertical
AC or DC AC AC or DC AC or touching touching or AC or DC flat AC flat AC trefoil
trefoil
1.5 14.5 13.5 17.5 15.5 20 18 - - - - -
2.5 20 18 24 21 27 25 - - - - -
4 26 24 32 28 37 33 - - - - -
6 34 31 41 36 47 43 - - - - -
10 46 42 57 50 65 59 - - - - -
16 61 56 76 68 87 79 - - - - -
25 80 73 101 89 114 104 131 114 110 146 130
35 99 89 125 110 141 129 162 143 137 181 162
50 119 108 151 134 182 167 196 174 167 219 197
70 151 136 192 171 234 214 251 225 216 281 254
95 182 164 232 207 284 261 304 275 264 341 311
120 210 188 269 239 330 303 352 321 308 396 362
150 240 216 300 262 381 349 406 372 356 456 419
185 273 245 341 296 436 400 463 427 409 521 480
240 321 286 400 346 515 472 546 507 485 615 569
300 367 328 458 394 594 545 629 587 561 709 659
400 - - 546 467 694 634 754 689 656 852 795
500 - - 626 533 792 723 868 789 749 982 920
630 - - 720 611 904 826 1005 905 855 1138 1070

Ambient temperature: 30ºC

Conductor operating temperature: 70ºC

The above table is in accordance with Table 4D1A of the 17th Edition of IEE Wiring Regulations.

Voltage Drop

NOMINAL CROSS SECTIONAL AREA

mm²

2 CABLES DC

mV/A/m

2 CABLES SINGLE-PHASE AC

mV/A/m

3 OR 4 CABLES THREE-PHASE AC

mV/A/m

Reference Methods A and B

(enclosed in conduit or trunking)

Reference Methods C, F (clipped direct, on tray or in free air)

Reference Methods A and B

(enclosed in conduit

or trunking)

Reference Methods C, F (clipped direct, on tray or in free air)

Cable

Touching

Cable

Spaced

Cable Touching Trefoil

Cable

Touching Flat

Cable

Spaced*

Flat

1.5 28 29 29 29 25 25 25 25
2.5 18 18 18 18 15 15 15 15
4 11 11 11 11 9.5 9.5 9.5 9.5
6 7.3 7.3 7.3 7.3 6.4 6.4 6.4 6.4
10 4.4 4.4 4.4 4.4 3.8 3.8 3.8 3.8
16 2.8 2.8 2.8 2.8 2.4 2.4 2.4 2.4
r x z r x z r x z r x z r x z r x z r x z
25 1.75 1.80 0.33 1.80 1.75 0.20 1.75 1.75 0.29 1.80 1.50 0.29 1.55 1.50 0.18 1.50 0.15 0.25 1.55 1.50 0.32 1.55
35 1.25 1.30 0.31 1.30 1.25 0.20 1.25 1.25 0.28 1.30 1.10 0.27 1.10 1.10 0.17 1.10 1.10 0.24 1.10 1.10 0.32 1.15
50 0.93 0.95 0.30 1.00 0.93 0.19 0.95 0.93 0.28 0.97 0.81 0.26 0.85 0.80 0.17 0.82 0.80 0.24 0.84 0.80 0.32 0.86
70 0.63 0.65 0.29 0.72 0.63 0.19 0.66 0.63 0.27 0.69 0.56 0.25 0.61 0.55 0.16 0.57 0.55 0.24 0.60 0.55 0.31 0.63
95 0.46 0.49 0.28 0.56 0.47 0.18 0.50 0.47 0.27 0.54 0.42 0.24 0.48 0.41 0.16 0.43 0.41 0.23 0.47 0.40 0.31 0.51
120 0.36 0.39 0.27 0.47 0.37 0.18 0.41 0.37 0.26 0.45 0.33 0.23 0.41 0.32 0.15 0.36 0.32 0.23 0.40 0.32 0.30 0.44
150 0.29 0.31 0.27 0.41 0.30 0.18 0.34 0.29 0.26 0.39 0.27 0.23 0.36 0.26 0.15 0.30 0.26 0.23 0.34 0.26 0.30 0.40
185 0.23 0.25 0.27 0.37 0.24 0.17 0.29 0.24 0.26 0.35 0.22 0.23 0.32 0.21 0.15 0.26 0.21 0.22 0.31 0.21 0.30 0.36
240 0.18 0.20 0.26 0.33 0.19 0.17 0.25 0.19 0.25 0.31 0.17 0.23 0.29 0.16 0.15 0.22 0.16 0.22 0.27 0.16 0.29 0.34
300 0.15 0.16 0.26 0.31 0.15 0.17 0.22 0.15 0.25 0.29 0.14 0.23 0.27 0.13 0.14 0.19 0.13 0.22 0.25 0.13 0.29 0.32
400 0.11 0.13 0.26 0.29 0.12 0.16 0.20 0.12 0.25 0.27 0.12 0.22 0.25 0.11 0.14 0.18 0.11 0.21 0.24 0.10 0.29 0.31
500 0.086 0.11 0.26 0.28 0.98 0.155 0.185 0.093 0.24 0.26 0.10 0.22 0.25 0.086 0.135 0.16 0.086 0.21 0.23 0.081 0.29 0.30
630 0.068 0.094 0.25 0.27 0.081 0.155 0.175 0.076 0.24 0.25 0.08 0.22 0.24 0.072 0.135 0.15 0.072 0.21 0.22 0.066 0.28 0.29

Conductor operating temperature: 70ºC

r = Resistive Component x = Reactive Component z = Impedance Value

*Spacings larger than one cable diameter will result in a larger voltage drop.

The above table is in accordance with Table 4D1B of the 17th Edition of IEE Wiring Regulations.

For cables having conductors of 16mm2 or less cross sectional area their inductances can be ignored and (mV/A/m)r values only are tabulated. For cables having conductors greater than 16mm2, cross sectional area the impedance values are given as (mV/A/m)z, together with the resistive component (mV/A/m)r and the reactive component (mV/A/m)x.

The above paragraph is extracted from Appendix 4 of the 17th Edition of IEE Wiring Regulations.

DE-RATING FACTORS

For Ambient Air Temperatures other than 30ºC

AMBIENT TEMPERATURE 25ºC 30ºC 35ºC 40ºC 45ºC 50ºC 55ºC
DE-RATING FACTOR 1.03 1.00 0.94 0.87 0.79 0.71 0.61

The information contained within this datasheet is for guidance only and is subject to change without notice or liability. All the information is provided in good faith and is believed to be correct at the time of publication. When selecting cable accessories, please note that actual cable dimensions may vary due to manufacturing tolerances.