6491X / H07V-R / H07V-U / BS EN 50525-2-31 Cable
APPLICATION
6491X Cable H07V-R/H07V-U is suitable for power and lighting circuits and building wiring. The cable is intended for use in semi-flush exposed conduits and embedded conduits as well as in closed installation ducts, and is ideal for the internal wiring of appliances.
CONSTRUCTION
Conductor
H07V-R: Class 2 stranded copper conductor to BS EN 60228 (previously BS 6360)
H07V-U: Class 1 solid copper conductor to BS EN 60228 (previously BS 6360)
Insulation
PVC (Polyvinyl Chloride) Type TI1 according to BS EN 50363
CABLE STANDARDS
BS EN 50525-2-31 (previously BS 6004) BASEC approved, BS EN/IEC 60332-1-2
The electrical and dimensional properties of this product are measured by the Technical and Quality Assurance department at the Sunwin Cables laboratory.
Cable performance in respect of conductor resistance, construction quality (workmanship),dimensional consistency, and other parameters are verified to published standardsand approved product drawings. Conformance to RoHS (Restriction of the use ofHazardous Substances) is determined and confirmed.
Voltage Rating (Uo/U) 450/750V
-15°C to +70°C
Minimum Bending Radius
Up to 10mm²: 3 x overall diameter 10mm² to 25mm²: 4 x overall diameter Above 25mm²: 5 x overall diameter
Insulation Colour
Red Black Blue Yellow White Green/Yellow Grey Brown
DIMENSIONS
Sunwin PART NO. |
NOMINAL CROSS SECTIONAL AREA mm² |
NOMINAL THICKNESS OF INSULATION mm |
NOMINAL OVERALL DIAMETER mm |
NOMINAL WEIGHT kg/km |
A2X*0015 | 1.5 | 0.7 | 2.9 | 22 |
A2X*0025 | 2.5 | 0.8 | 3.6 | 32 |
A2X*0040 | 4 | 0.8 | 4.1 | 50 |
A2X*0060 | 6 | 0.8 | 4.7 | 71 |
A2X*010 | 10 | 1 | 5.9 | 110 |
A2X*016 | 16 | 1 | 6.8 | 164 |
A2X*025 | 25 | 1.2 | 8.4 | 256 |
A2X*035 | 35 | 1.2 | 9.4 | 346 |
A2X*050 | 50 | 1.4 | 11 | 473 |
A2X*070 | 70 | 1.4 | 12.7 | 674 |
A2X*095 | 95 | 1.6 | 14.7 | 913 |
A2X*120 | 120 | 1.6 | 16.2 | 1150 |
A2X*150 | 150 | 1.8 | 18 | 1416 |
A2X*185 | 185 | 2 | 20 | 1749 |
A2X*240 | 240 | 2.2 | 23 | 2317 |
A2X*300 | 300 | 2.4 | 25.2 | 3049 |
A2X*400 | 400 | 2.6 | 28.4 | 3657 |
A2X*500 | 500 | 2.8 | 31.8 | 4700 |
A2X*630 | 630 | 2.8 | 38.1 | 5890 |
* Sunwin Part No. shown above designate the sheath colour (*). For each colour substitute * for a colour code as listed below. e.g. A2XRD0040 = 4mm2 Red
Colour Codes
COLOUR | Black | Blue | Grey | Green/Yellow | Red | Yellow | Brown | White |
CODE | BK | BL | GR | GY | RD | YW | BR | WH |
CONDUCTORS
Class 2 Stranded Conductors for Single Core and Multi-Core Cables
NOMINAL CROSS SECTIONAL AREA mm² |
MINIMUM NO. OF WIRES IN CONDUCTOR | MAXIMUM RESISTANCE OF CONDUCTOR AT 20ºC | |||||
Circular | Circular Compacted | Shaped | Annealed Copper Conductor | ||||
Cu | Al | Cu | Al | Cu | Al |
Plain Wires ohms/km |
|
1.5 | 7 | - | 6 | - | - | - | 12.1 |
2.5 | 7 | - | 6 | - | - | - | 7.41 |
4 | 7 | - | 6 | - | - | - | 4.61 |
6 | 7 | - | 6 | - | - | - | 3.08 |
10 | 7 | 7 | 6 | 6 | - | - | 1.83 |
16 | 7 | 7 | 6 | 6 | - | - | 1.15 |
25 | 7 | 7 | 6 | 6 | 6 | 6 | 0.727 |
35 | 7 | 7 | 6 | 6 | 6 | 6 | 0.524 |
50 | 19 | 19 | 6 | 6 | 6 | 6 | 0.387 |
70 | 19 | 19 | 12 | 12 | 12 | 12 | 0.268 |
95 | 19 | 19 | 15 | 15 | 15 | 15 | 0.193 |
120 | 37 | 37 | 18 | 15 | 18 | 15 | 0.153 |
150 | 37 | 37 | 18 | 15 | 18 | 15 | 0.124 |
185 | 37 | 37 | 30 | 30 | 30 | 30 | 0.0991 |
240 | 37 | 37 | 34 | 30 | 34 | 30 | 0.0754 |
300 | 61 | 61 | 34 | 30 | 34 | 30 | 0.0601 |
400 | 61 | 61 | 53 | 53 | 53 | 53 | 0.047 |
500 | 61 | 61 | 53 | 53 | 53 | 53 | 0.0366 |
630 | 91 | 91 | 53 | 53 | 53 | 53 | 0.0283 |
The above table is in accordance with BS EN 60228 (previously BS 6360)
Current Carrying Capacity
NOMINAL CROSS | REFERENCE METHOD A | REFERENCE METHOD B | REFERENCE METHOD C | REFERENCE METHOD F | |||||||
SECTIONAL AREA | (ENCLOSED IN CONDUIT | (ENCLOSED IN CONDUIT | (CLIPPED DIRECT) |
(IN FREE AIR OR ON A PERFORATED CABLE TRAY ETC HORIZONTAL |
|||||||
mm² | IN THERMALLY | ON A WALL OR IN A | Amps | OR VERTICAL ETC) | |||||||
INSULATING WALL ETC) | TRUNKING ETC) | Amps | |||||||||
Amps | Amps | ||||||||||
Touching |
Spaced by one diameter | ||||||||||
2 Cables Single-Phase AC or DC or 3 Cables Three-Phase AC flat |
|||||||||||
2 Cables | 3 or 4 Cables | ||||||||||
2 Cables | 3 or 4 Cables | 2 Cables | 3 or 4 Cables |
Single- Phase |
Three- Phase |
2 Cables | 3 Cables | 3 Cables | |||
Single- Phase |
Three- Phase |
Single- Phase |
Three- Phase |
AC or DC flat | AC flat and |
Single- Phase |
Three- Phase |
Three- Phase |
Horizontal | Vertical | |
AC or DC | AC | AC or DC | AC | or touching | touching or | AC or DC flat | AC flat | AC trefoil | |||
trefoil | |||||||||||
1.5 | 14.5 | 13.5 | 17.5 | 15.5 | 20 | 18 | - | - | - | - | - |
2.5 | 20 | 18 | 24 | 21 | 27 | 25 | - | - | - | - | - |
4 | 26 | 24 | 32 | 28 | 37 | 33 | - | - | - | - | - |
6 | 34 | 31 | 41 | 36 | 47 | 43 | - | - | - | - | - |
10 | 46 | 42 | 57 | 50 | 65 | 59 | - | - | - | - | - |
16 | 61 | 56 | 76 | 68 | 87 | 79 | - | - | - | - | - |
25 | 80 | 73 | 101 | 89 | 114 | 104 | 131 | 114 | 110 | 146 | 130 |
35 | 99 | 89 | 125 | 110 | 141 | 129 | 162 | 143 | 137 | 181 | 162 |
50 | 119 | 108 | 151 | 134 | 182 | 167 | 196 | 174 | 167 | 219 | 197 |
70 | 151 | 136 | 192 | 171 | 234 | 214 | 251 | 225 | 216 | 281 | 254 |
95 | 182 | 164 | 232 | 207 | 284 | 261 | 304 | 275 | 264 | 341 | 311 |
120 | 210 | 188 | 269 | 239 | 330 | 303 | 352 | 321 | 308 | 396 | 362 |
150 | 240 | 216 | 300 | 262 | 381 | 349 | 406 | 372 | 356 | 456 | 419 |
185 | 273 | 245 | 341 | 296 | 436 | 400 | 463 | 427 | 409 | 521 | 480 |
240 | 321 | 286 | 400 | 346 | 515 | 472 | 546 | 507 | 485 | 615 | 569 |
300 | 367 | 328 | 458 | 394 | 594 | 545 | 629 | 587 | 561 | 709 | 659 |
400 | - | - | 546 | 467 | 694 | 634 | 754 | 689 | 656 | 852 | 795 |
500 | - | - | 626 | 533 | 792 | 723 | 868 | 789 | 749 | 982 | 920 |
630 | - | - | 720 | 611 | 904 | 826 | 1005 | 905 | 855 | 1138 | 1070 |
Ambient temperature: 30ºC
Conductor operating temperature: 70ºC
The above table is in accordance with Table 4D1A of the 17th Edition of IEE Wiring Regulations.
Voltage Drop
NOMINAL CROSS SECTIONAL AREA mm² |
2 CABLES DC mV/A/m |
2 CABLES SINGLE-PHASE AC mV/A/m |
3 OR 4 CABLES THREE-PHASE AC mV/A/m |
|||||||||||||||||||
Reference Methods A and B (enclosed in conduit or trunking) |
Reference Methods C, F (clipped direct, on tray or in free air) |
Reference Methods A and B (enclosed in conduit or trunking) |
Reference Methods C, F (clipped direct, on tray or in free air) |
|||||||||||||||||||
Cable Touching |
Cable Spaced |
Cable Touching Trefoil |
Cable Touching Flat |
Cable Spaced* Flat |
||||||||||||||||||
1.5 | 28 | 29 | 29 | 29 | 25 | 25 | 25 | 25 | ||||||||||||||
2.5 | 18 | 18 | 18 | 18 | 15 | 15 | 15 | 15 | ||||||||||||||
4 | 11 | 11 | 11 | 11 | 9.5 | 9.5 | 9.5 | 9.5 | ||||||||||||||
6 | 7.3 | 7.3 | 7.3 | 7.3 | 6.4 | 6.4 | 6.4 | 6.4 | ||||||||||||||
10 | 4.4 | 4.4 | 4.4 | 4.4 | 3.8 | 3.8 | 3.8 | 3.8 | ||||||||||||||
16 | 2.8 | 2.8 | 2.8 | 2.8 | 2.4 | 2.4 | 2.4 | 2.4 | ||||||||||||||
r | x | z | r | x | z | r | x | z | r | x | z | r | x | z | r | x | z | r | x | z | ||
25 | 1.75 | 1.80 | 0.33 | 1.80 | 1.75 | 0.20 | 1.75 | 1.75 | 0.29 | 1.80 | 1.50 | 0.29 | 1.55 | 1.50 | 0.18 | 1.50 | 0.15 | 0.25 | 1.55 | 1.50 | 0.32 | 1.55 |
35 | 1.25 | 1.30 | 0.31 | 1.30 | 1.25 | 0.20 | 1.25 | 1.25 | 0.28 | 1.30 | 1.10 | 0.27 | 1.10 | 1.10 | 0.17 | 1.10 | 1.10 | 0.24 | 1.10 | 1.10 | 0.32 | 1.15 |
50 | 0.93 | 0.95 | 0.30 | 1.00 | 0.93 | 0.19 | 0.95 | 0.93 | 0.28 | 0.97 | 0.81 | 0.26 | 0.85 | 0.80 | 0.17 | 0.82 | 0.80 | 0.24 | 0.84 | 0.80 | 0.32 | 0.86 |
70 | 0.63 | 0.65 | 0.29 | 0.72 | 0.63 | 0.19 | 0.66 | 0.63 | 0.27 | 0.69 | 0.56 | 0.25 | 0.61 | 0.55 | 0.16 | 0.57 | 0.55 | 0.24 | 0.60 | 0.55 | 0.31 | 0.63 |
95 | 0.46 | 0.49 | 0.28 | 0.56 | 0.47 | 0.18 | 0.50 | 0.47 | 0.27 | 0.54 | 0.42 | 0.24 | 0.48 | 0.41 | 0.16 | 0.43 | 0.41 | 0.23 | 0.47 | 0.40 | 0.31 | 0.51 |
120 | 0.36 | 0.39 | 0.27 | 0.47 | 0.37 | 0.18 | 0.41 | 0.37 | 0.26 | 0.45 | 0.33 | 0.23 | 0.41 | 0.32 | 0.15 | 0.36 | 0.32 | 0.23 | 0.40 | 0.32 | 0.30 | 0.44 |
150 | 0.29 | 0.31 | 0.27 | 0.41 | 0.30 | 0.18 | 0.34 | 0.29 | 0.26 | 0.39 | 0.27 | 0.23 | 0.36 | 0.26 | 0.15 | 0.30 | 0.26 | 0.23 | 0.34 | 0.26 | 0.30 | 0.40 |
185 | 0.23 | 0.25 | 0.27 | 0.37 | 0.24 | 0.17 | 0.29 | 0.24 | 0.26 | 0.35 | 0.22 | 0.23 | 0.32 | 0.21 | 0.15 | 0.26 | 0.21 | 0.22 | 0.31 | 0.21 | 0.30 | 0.36 |
240 | 0.18 | 0.20 | 0.26 | 0.33 | 0.19 | 0.17 | 0.25 | 0.19 | 0.25 | 0.31 | 0.17 | 0.23 | 0.29 | 0.16 | 0.15 | 0.22 | 0.16 | 0.22 | 0.27 | 0.16 | 0.29 | 0.34 |
300 | 0.15 | 0.16 | 0.26 | 0.31 | 0.15 | 0.17 | 0.22 | 0.15 | 0.25 | 0.29 | 0.14 | 0.23 | 0.27 | 0.13 | 0.14 | 0.19 | 0.13 | 0.22 | 0.25 | 0.13 | 0.29 | 0.32 |
400 | 0.11 | 0.13 | 0.26 | 0.29 | 0.12 | 0.16 | 0.20 | 0.12 | 0.25 | 0.27 | 0.12 | 0.22 | 0.25 | 0.11 | 0.14 | 0.18 | 0.11 | 0.21 | 0.24 | 0.10 | 0.29 | 0.31 |
500 | 0.086 | 0.11 | 0.26 | 0.28 | 0.98 | 0.155 | 0.185 | 0.093 | 0.24 | 0.26 | 0.10 | 0.22 | 0.25 | 0.086 | 0.135 | 0.16 | 0.086 | 0.21 | 0.23 | 0.081 | 0.29 | 0.30 |
630 | 0.068 | 0.094 | 0.25 | 0.27 | 0.081 | 0.155 | 0.175 | 0.076 | 0.24 | 0.25 | 0.08 | 0.22 | 0.24 | 0.072 | 0.135 | 0.15 | 0.072 | 0.21 | 0.22 | 0.066 | 0.28 | 0.29 |
Conductor operating temperature: 70ºC
r = Resistive Component x = Reactive Component z = Impedance Value
*Spacings larger than one cable diameter will result in a larger voltage drop.
The above table is in accordance with Table 4D1B of the 17th Edition of IEE Wiring Regulations.
For cables having conductors of 16mm2 or less cross sectional area their inductances can be ignored and (mV/A/m)r values only are tabulated. For cables having conductors greater than 16mm2, cross sectional area the impedance values are given as (mV/A/m)z, together with the resistive component (mV/A/m)r and the reactive component (mV/A/m)x.
The above paragraph is extracted from Appendix 4 of the 17th Edition of IEE Wiring Regulations.
For Ambient Air Temperatures other than 30ºC
AMBIENT TEMPERATURE | 25ºC | 30ºC | 35ºC | 40ºC | 45ºC | 50ºC | 55ºC |
DE-RATING FACTOR | 1.03 | 1.00 | 0.94 | 0.87 | 0.79 | 0.71 | 0.61 |
The information contained within this datasheet is for guidance only and is subject to change without notice or liability. All the information is provided in good faith and is believed to be correct at the time of publication. When selecting cable accessories, please note that actual cable dimensions may vary due to manufacturing tolerances.