Add to Cart
Low Smoke Zero Halogen Mineral Insulated Cable Mi Wire High Temperature
APPLICATION
A 500V light duty low smoke zero halogen, mineral insulated cable designed to give ultimate fire performance. Used
for power and control circuits providing circuit integrity to 950°C. Suitable for oil, gas and petroleum industries, airports, emergency lighting systems and fire alarm systems.
CONSTRUCTION
Solid plain copper conductor
Magnesium Oxide
Copper tube, LSZH (Low Smoke Zero Halogen)
CABLE STANDARDS
BS EN60702 Part 1, BS 5839-1 Enhanced (26.2e) BS 5266, BS 8519 Cat 1 and 2
BS 8434-2, BS EN 50200-PH30, PH60, PH120 BS 6387 C, W and Z, BS 8491
BS EN 50267, BS EN 50268
BS EN 50265 and 50266
The electrical and dimensional properties of this product are measured by the Technical and Quality Assurance department at the Sunwin Cables laboratory.
Cable performance in respect of conductor resistance, construction quality (workmanship),dimensional consistency, and other parameters are verified to published standardsand approved product drawings. Conformance to RoHS (Restriction of the use ofHazardous Substances) is determined and confirmed.
CHARACTERISTICS
500V
-10°C to 250°C
6 x overall diameter
Red White Orange
Other colour available on request
DIMENSIONS
Sunwin PART NO. | NO. OF CORES |
NOMINAL CROSS SECTIONAL AREA mm² |
NOMINAL OVERALL DIAMETER mm |
NOMINAL WEIGHT kg/km |
A6M02010** | 2 | 1 | 6.4 | 126 |
A6M02015** | 2 | 1.5 | 7 | 154 |
A6M02025** | 2 | 2.5 | 7.9 | 206 |
A6M02040** | 2 | 4 | 9.2 | 322 |
A6M03010** | 3 | 1 | 7.1 | 159 |
A6M03015** | 3 | 1.5 | 7.7 | 194 |
A6M03025** | 3 | 2.5 | 8.8 | 272 |
A6M04010** | 4 | 1 | 7.6 | 187 |
A6M04015** | 4 | 1.5 | 8.3 | 231 |
A6M04025** | 4 | 2.5 | 9.6 | 336 |
A6M07015** | 7 1.5 | 9.9 | 351 | |
A6M07025** | 7 | 2.5 | 11.2 | 475 |
* Sunwin Part No. shown above designate the sheath colour (*). For each colour substitute * for a colour code as listed below. e.g. A6M02010RD = 1mm2 Red
Colour Codes
COLOUR | Red | Orange | White |
CODE | RD | OR | WH |
CONDUCTORS
NOMINAL CROSS SECTIONAL AREA mm² |
MAXIMUM RESISTANCE OF CONDUCTOR AT 20ºC ohms/km |
1 | 18.1 |
1.5 | 12.1 |
2.5 | 7.41 |
4 | 4.61 |
ELECTRICAL CHARACTERISTICS
Current Carrying Capacity
NO. OF CORES |
NOMINAL CROSS SECTIONAL AREA mm² |
SINGLE PHASE AC OR DC Amps |
THREE PHASE AC Amps |
2 | 1 | 18.5 | - |
2 | 1.5 | 23 | - |
2 | 2.5 | 31 | - |
2 | 4 | 40 | - |
3 | 1 | - | 15 |
3 | 1.5 | - | 19 |
3 | 2.5 | - | 26 |
4 | 1 | - | 15 |
4 | 1.5 | - | 19 |
4 | 2.5 | - | 26 |
7 | 1.5 | 13 | - |
7 | 2.5 | 17.5 | - |
Voltage Drop
NO. OF CORES |
NOMINAL CROSS SECTIONAL AREA mm² |
SINGLE PHASE AC OR DC mV/A/M |
THREE PHASE AC mV/A/M |
2 | 1 | 42 | - |
2 | 1.5 | 28 | - |
2 | 2.5 | 17 | - |
2 | 4 | 10 | - |
3 | 1 | - | 36 |
3 | 1.5 | - | 24 |
3 | 2.5 | - | 14 |
4 | 1 | - | 36 |
4 | 1.5 | - | 24 |
4 | 2.5 | - | 14 |
7 | 1.5 | 28 | - |
7 | 2.5 | 17 | - |
* Method of cable support should withstand a similar temperature and duration to that of the cable.
The information contained within this datasheet is for guidance only and is subject to change without notice or liability. All the information is provided in good faith and is believed to be correct at the time of publication. When selecting cable accessories, please note that actual cable dimensions may vary due to manufacturing tolerances.