Heavy Load 750V Mineral Insulated Copper Sheathed Cable Smoke Free Non Toxicity
APPLICATION
A 500V light duty mineral insulated cable designed to give the ultimate fire performance. Used in power and control circuits providing circuit integrity to 950°C. Suitable for Oil, Gas and Petroleum industries, airports, emergency lighting system and fire alarm systems.
CONSTRUCTION
Conductor
Class 1 Solid plain copper conductor
Magnesium Oxide
Plain copper
BS EN 60702 Part 1
BS 5266, BS 8519 Cat 1 and 2, BS 8434-2, BS 6387 C, W and Z
BS 8491, BS EN 50200-PH30/60/120
BS 5839-1 Enhanced (26.2e)
The electrical and dimensional properties of this product are measured by the Technical and Quality Assurance department at the Sunwin Cables laboratory.
Cable performance in respect of conductor resistance, construction quality (workmanship),dimensional consistency, and other parameters are verified to published standardsand approved product drawings. Conformance to RoHS (Restriction of the use ofHazardous Substances) is determined and confirmed.
CHARACTERISTICS
500V
-10°C to 250°C
6 x overall diameter
Plain copper
DIMENSIONS
Sunwin PART NO. | NO. OF CORES |
NOMINAL CROSS SECTIONAL AREA mm² |
NOMINAL OVERALL DIAMETER mm |
NOMINAL WEIGHT kg/km |
A6M020010PC | 2 | 1 | 5.1 | 105 |
A6M020015PC | 2 | 1.5 | 5.7 | 131 |
A6M020025PC | 2 | 2.5 | 6.6 | 180 |
A6M02004PC | 2 | 4 | 7.7 | 262 |
A6M030010PC | 3 | 1 | 5.8 | 136 |
A6M030015PC | 3 | 1.5 | 6.4 | 168 |
A6M030025PC | 3 | 2.5 | 7.3 | 222 |
A6M040010PC | 4 | 1 | 6.3 | 162 |
A6M040015PC | 4 | 1.5 | 7 | 203 |
A6M040025PC | 4 | 2.5 | 8.1 | 286 |
A6M070015PC | 7 | 1.5 | 8.4 | 310 |
A6M070025PC | 7 | 2.5 | 9.7 | 433 |
CONDUCTORS
NOMINAL CROSS SECTIONAL AREA mm² |
MAXIMUM RESISTANCE OF CONDUCTOR AT 20ºC ohms/km |
1 | 18.1 |
1.5 | 12.1 |
2.5 | 7.41 |
4 | 4.61 |
ELECTRICAL CHARACTERISTICS
Current Carrying Capacity
NO. OF CORES |
NOMINAL CROSS SECTIONAL AREA mm² |
SINGLE PHASE AC OR DC Amps |
THREE PHASE AC Amps |
2 | 1 | 17 | - |
2 | 1.5 | 21 | - |
2 | 2.5 | 28 | - |
2 | 4 | 36 | - |
3 | 1 | - | 14 |
3 | 1.5 | - | 17 |
3 | 2.5 | - | 23 |
4 | 1 | - | 14 |
4 | 1.5 | - | 17 |
4 | 2.5 | - | 23 |
7 | 1.5 | 12 | - |
7 | 2.5 | 16 | - |
Voltage Drop
NO. OF CORES |
NOMINAL CROSS SECTIONAL AREA mm² |
SINGLE PHASE AC OR DC mV/A/M |
THREE PHASE AC mV/A/M |
2 | 1 | 42 | - |
2 | 1.5 | 28 | - |
2 | 2.5 | 17 | - |
2 | 4 | 10 | - |
3 | 1 | - | 36 |
3 | 1.5 | - | 24 |
3 | 2.5 | - | 14 |
4 | 1 | - | 36 |
4 | 1.5 | - | 24 |
4 | 2.5 | - | 14 |
7 | 1.5 | 28 | - |
7 | 2.5 | 17 | - |
* Method of cable support should withstand a similar temperature and donation to that of the cable.
The information contained within this datasheet is for guidance only and is subject to change without notice or liability. All the information is provided in good faith and is believed to be correct at the time of publication. When selecting cable accessories, please note that actual cable dimensions may vary due to manufacturing tolerances.