Bare Copper Security Low Voltage Power Cable With Improved Fire Characteristics
Technical data
max. 73,2 Ohm/km
flexing -5°C to +50°C
fixed installation -30°C to +70°C
225 V (not for purposes of
high current and power installation)
core/core 500 V
core/screen 2000 V
max. 120 nF/km at 800 Hz (this values may be extended at
20% with a make-up up to 4 pairs)
max. 200 pF/100 m
(20% of the values, but one value up to 400 pF is allowed)
6x cable Ø
see Technical Informations
Cable structure
0,8 mm Ø Outer sheath halogen-free, flame retardant to DIN VDE 0207 part 24 HM2
Tests
IEC 60332-3 (previously DIN VDE 0472 part 804 test method C)
Corrosiveness of combustion gases
acc. to DIN VDE 0482 part 267,
DIN EN 50267-2-2, IEC 60754-2
(equivalent DIN VDE 0472 part 813)
systems for minimum 90 minutes. Test method to DIN 4102 part 12.
Properties
Insulation integrity under direct flame propagation for the test period of 180 minutes.
The functionality for 30 minutes assures
when persons and animals are to be saved
from a burning building. 30 minutes secures the functional performance of the fire warning and alarm systems, safety and spare lighting, passenger lifts with evacuation circuits, except the cables which are installed within the ladder shafts and engine rooms.
E 90: Functionality of electrical cable
systems for minimum 90 minutes. Test method to DIN 4102 part 12.
(equivalent DIN VDE 0472 part 813)
Note
Application
Flame resistant, halogen-free, static screened installation cables for telecommunication purpose. The static screen prevents strong interference impulse. Suitable for fixed installation everywhere, where in case of fire human life and material assets are to be protected and a safety conciousness take a special significance, e. g. in industrial complexes, public buildings, hotels, airports, under ground railway networks, hospitals.
CE= The product is conformed with the EC Low-Voltage Directive 2006/95/EC.