Add to Cart
Black Underground Low Voltage Power Cable Bare Copper Conductor 6/1 KV
Technical data
DIN VDE 0266
-30°C to +70°C
at conductor +90°C
Minimum bending radius :15x cable Ø
up to 200x106 cJ/kg (up to 200 Mrad)
see Technical Informations
Cable structure
DIN VDE 0295 cl.1 or cl.2, single-wire or multi-wire, BS 6360 cl.1 or cl.2, IEC 60228 cl.1 or cl.2
Core insulation of polymer
Outer sheath of polyolefin-compound, flame retardant
Tests
DIN VDE 0482-332-3, BS 4066 part 3,
DIN EN 60332-3, IEC 60332-3 (previously
DIN VDE 0472 part 804 test method C)
DIN EN 50267-2-2, IEC 60754-2
(equivalent DIN VDE 0472 part 813)
part 267, DIN EN 50267-2-1, IEC 60754-1
(equivalent DIN VDE 0472 part 815)
IEC 61034-1+2, BS 7622 part 1+2
(previously DIN VDE 0472 part 816)
Properties
Low smoke density, no darkening of emergency exits without hindering the fire extinguishing works
Insulation integrity under direct flame propagation for the test period of 180 minutes.
Note
Application
Security cables are ideal for use everywhere, where in case of fire human life and material assets are to be protected and safety conciousness take a special significance, e. g. in industrial complexes, power stations, communal establishment, hotels, airports, underground railway networks, hospitals and outpatients clinic (DIN VDE 0107), department stores, data processing centres, theaters, cinemas, in multi-storey buildings, public gatherings, schools etc. (DIN VDE 0108), mining works, offshore plants, leading centres, traffic communication, emergency power supply and alarm systems. The cables are suitable for fixed installation in dry and moist rooms, in, above, on and beneath plaster as well as in masonary walls and in concrete. These cables are suitable for outdoor applications and in underground by using in conduits or tubes. For the installation in conduit all precautions must be taken that no accumulation of water can occur in the pipes.
CE= The product is conformed with the EC Low-Voltage Directive 2006/95/EC.
Part no. | No.cores x cross-sec. mm² | Outer Ø app. mm | Cop. weight kg / km |
Weight app. kg / km |
AWG-No. |
52700 | 1 x 4 re | 7,0 | 38,0 | 98,0 | 12 |
52701 | 1 x 6 re | 7,5 | 58,0 | 125,0 | 10 |
52702 | 1 x 10 re | 8,0 | 96,0 | 165,0 | 8 |
52703 | 1 x 16 rm | 9,0 | 154,0 | 230,0 | 6 |
52704 | 1 x 25 rm | 10,5 | 240,0 | 345,0 | 4 |
52705 | 1 x 35 rm | 11,5 | 336,0 | 450,0 | 2 |
52706 | 1 x 50 rm | 12,0 | 480,0 | 590,0 | 1 |
Part no. No.cores x cross-sec. mm² |
Outer Ø app. mm | Cop. weight kg / km |
Weight app. kg / km |
AWG-No. |
52707 1 x 70 rm | 15,0 | 672,0 | 800,0 | 2/0 |
52708 1 x 95 rm | 16,5 | 912,0 | 1100,0 | 3/0 |
52709 1 x 120 rm | 18,5 | 1152,0 | 1350,0 | 4/0 |
52710 1 x 150 rm | 20,5 | 1440,0 | 1650,0 | 300 kcmil |
52711 1 x 185 rm | 23,0 | 1776,0 | 2000,0 | 350 kcmil |
52712 1 x 240 rm | 25,5 | 2304,0 | 2650,0 | 500 kcmil |
52713 1 x 300 rm | 31,8 | 2880,0 | 3200,0 |
600 kcmil Continuation |
Part no. | No.cores x | Outer Ø | Cop. | Weight | AWG-No. | Part no. No.cores x | Outer Ø Cop. Weight AWG-No. | |
cross-sec. | app. mm | weight | app. kg / km | cross-sec. | app. mm weight app. kg / km | |||
mm² | kg / km | mm² | kg / km |
52715 52716 |
2 x 4 re 2 x 6 re |
13,5 14,5 |
77,0 115,0 |
345,0 410,0 |
12 10 |
52749 52750 |
5 x 1,5 re 5 x 2,5 re |
14,0 15,0 |
72,0 120,0 |
375,0 445,0 |
16 14 |
|
52717 | 2 x 10 re | 16,0 | 192,0 | 540,0 | 8 | 52751 | 5 x 4 re | 16,5 | 192,0 | 560,0 | 12 | |
52718 | 2 x 16 rm | 18,0 | 307,0 | 720,0 | 6 | 52752 | 5 x 6 re | 18,0 | 288,0 | 690,0 | 10 | |
52719 | 2 x 25 rm | 21,0 | 480,0 | 1100,0 | 4 | 52753 | 5 x 10 re | 20,0 | 480,0 | 950,0 | 8 |