High Tension Single Core Low Voltage Power Cable With Concentric Conductor
Technical data
Power and control cable acc. to DIN VDE 0276 part 604,
HD 604 S1 part 1 and part 5G
Temperature range
during installation -5°C to +50°C fixed installation -30°C to +90°C
Permissible operating temperature
at conductor +90°C
Nominal voltage U0/U 0,6/1 kV
Test voltage 4 kV
Minimum bending radius
single-core 15x cable Ø multi-core 12x cable Ø
Radiation resistance
up to 100x106 cJ/kg (up to 100 Mrad)
Caloric load values
see Technical Informations
Cable structure
Bare copper-conductor, to
DIN VDE 0295 cl.1 or cl.2, single-wire or multi-wire, BS 6360 cl.1 or cl.2, IEC 60228 cl.1 or cl.2
Core insulation of cross-linked polyethylene (XLPE)
compound type 2XI1 to HD 604 S1
Core identification to DIN VDE 0293-308
Core identification for 3+½ conductor J-type: GN-YE (½), BN, BK, GY
O-type: BU (½), BN, BK, GY
Cores stranded in layers (for multi-core cables)
Overall filled inner sheath
Covered by filling compound or taping
Outer sheath of thermoplastic polyolefine, compound type HM4 to HD 604 S1
Sheath colour black
Properties
Halogen-free, no separation of corrosive or toxic gases
Limited propagation of fire
Low smoke development
The materials used in manufacture are cadmium-free and contain no silicone and free from substances harmful to the wetting properties of lacquers tests
Flame test acc. to DIN VDE 0482-332-3-24, BS 4066 part 3, DIN EN 60332-3-24,
IEC 60332-3-24 (previously DIN VDE 0472
part 804 test method C)
Corrosiveness of combustion gases
acc. to DIN VDE 0482 part 267,
DIN EN 50267-2-2, IEC 60754-2
(equivalent DIN VDE 0472 part 813)
Halogen-free acc. to DIN VDE 0482
part 267, DIN EN 50267-2-1, IEC 60754-1
(equivalent DIN VDE 0472 part 815)
Smoke density acc. to DIN VDE 0482 part 1034-1+2, DIN EN 61034-1+2,
IEC 61034-1+2, BS 7622 part 1+2
(previously DIN VDE 0472 part 816)
Note
re = round conductor, single-wire rm = round conductor, multi-wire sm = sectional conductor, mutli-wire
J-version = with GN-YE conductor
O-version = without GN-YE conductor
AWG sizes are approximate equivalent values. The actual cross-section is in mm².
LS0H = Low Smoke Zero Halogen
Application
The power cables with enhanced characteristics in case of fire are used in power stations.
The concentric conductor can be used as a PE or PEN conductor or as screen. Suitable for fixed installation in dry, damp or wet environments, in, above, on and beneath plaster as well as in masonary walls and in concrete. These cables are suitable for outdoor applications and in underground by using in conduits or tubes. For the installation in conduit all precautions must be taken that no accumulation of water can occur in the pipes
CE= The product is conformed with the EC Low-Voltage Directive 2006/95/EC.
53243 | 21 x 2,5 / 6 re | 25,2 | 572,0 | 1015,0 | 14 |
53237 | 24 x 1,5 / 6 re | 23,2 | 412,0 | 800,0 | 16 |
53244 | 24 x 2,5 / 10 re | 26,1 | 695,0 | 1100,0 | 14 |
53238 | 30 x 1,5 / 6 re | 24,3 | 500,0 | 930,0 | 16 |
53245 | 30 x 2,5 / 10 re | 28,0 | 842,0 | 1290,0 | 14 |