3kV Flexible Low Voltage Power Cable EMC LSZH Screened Cable With Copper Conductor
TOXFREE ZH ROZ1-K AS VFD EMC 1,8/3kV cable has been specially designed for Variable Frequency Drive Motors and installations where it is necessary to limit the effects of electromagnetic interference (EMI).
Electrical performance
LOW VOLTAGE 0.6/1 (1,2) KV
Standard
IEC 60502-1 / IEC 60092-353
Approvals
CE
DNV-GL
ABS (in progress)
RoHS
Construction Product Regulation
Cca - s1a, d1, a2
Thermal performance
Maximum service temperature: 90ºC.
Maximum short-circuit temperature: 250ºC (max. 5 s).
Minimum service temperature: -40ºC (fixed and protected installations).
Fire performance
Flame non-propagation based on UNE-EN 60332-1 and IEC 60332-1.
Fire non-propagation based on UNE-EN 60332-3 and IEC 60332-3.
LSZH (Low Smoke Zero Halogen) based on UNE-EN 60754-1 and IEC 60754-1.
Low smoke emission based on UNE-EN 61034 and IEC 61034.: Light transmittance > 60%
Low corrosive gases emission based on UNE-EN 60754-2 and IEC 60754-2.
Mechanical performance
Minimum bending radius: x10 cable diameter.
Impact resistance: AG2 Medium severity.
Chemical performance
Chemical & Oil resistance: Good.
Water performance
Water resistance: AD5 Jets.
Other
Meter by meter marking.
Electric fields resistant.
Installation conditions
Open Air.
Buried.
In conduit.
Applications
Industrial use.
Variable Frequency Drive (VFD)
Conductor
Electrolytic copper, class 5 (flexible), based on EN 60228 and IEC 60228.
Grounding Conductor
The grounding conductor is divided into three conductors; the equivalent cross section is approximately 50% of the section of the phase conductor.
Insulation
Cross-linked polyethylene (XLPE)
The standard identification of insulated conductors is the following:
4G grey + brown + black + Green/yellow (up to 4 mm2)
3x + 3G grey + brown + black + Green/yellow (3 x) (from 6 mm2 onwards)
Screen
Aluminium-polyester tape screen, helically placed over the insulated conductors. Over the tape there is a tinned copper braid screen. The tape and the braid act as a double screen to cut out all of the the electromagnetic interference.
The screen has a cover of 100% and its total section is approximately 10% of one of the conductors.
Outer sheath
Polyolefin LSZH outer sheath, black colour.
Technology
1. Conductor
Electrolytic copper, class 5 (flexible), based on EN 60228 and IEC 60228.
2. Grounding Conductor
The grounding conductor is divided into three conductors; the equivalent cross section is approximately 50% of the section of the phase conductor.
3. Insulation
Cross-linked polyethylene (XLPE)
The standard identification of insulated conductors is the following:
4G grey + brown + black + yellow/green (up to 4 mm2)
3x + 3G grey + brown + black + yellow/green (3 x) (from 6 mm2 onwards)
4. Screen
Aluminium-polyester tape screen, helically placed over the insulated conductors. Over the tape there is a tinned copper braid screen. The tape and the braid act as a double screen to cut out all of the the electromagnetic interference.The screen has a cover of 100% and its total section is approximately 10% of one of the conductors.
5. Outer sheath
Polyolefin LSZH outer sheath, black colour.