Technical data:
Test voltage | 6 / 10 kV | [kV] | 21 / 5 min. |
12 / 20 kV | [kV] | 42 / 5 min. | |
18 / 30 kV | [kV] | 63 / 5 min. | |
Temperature range | in motion | -5°C till +70°C | |
fixed | -20°C till +70°C | ||
Operating temperature | short circuit | °C | 250 |
Short circuit time | max. | [sec] | 5 |
Bending radius | min. | x diameter | 15 |
Flammability | standard | EN 60332-1-2 |
Number of cores and nominal cross section mm2 |
Aluminium figure kg/km |
Copper figure kg/km |
Overall diameter appr. mm |
Overall diameter max. value appr. mm |
Weight appr. kg/km |
Current carrying capacity ground A |
Current carrying capacity air A |
|||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
1 x 50 RM/16 | 147,0 | 190 | 33 | 38 | 1.100,0 | 174 | 187 | |||||||
1 x 70 RM/16 | 206,0 | 190 | 35 | 40 | 1.200,0 | 213 | 232 | |||||||
1 x 95 RM/16 | 279,0 | 190 | 36 | 41 | 1.350,0 | 254 | 282 | |||||||
1 x 120 RM/16 | 353,0 | 190 | 38 | 43 | 1.450,0 | 289 | 325 | |||||||
1 x 150 RM/25 | 441,0 | 295 | 39 | 44 | 1.700,0 | 322 | 367 | |||||||
1 x 185 RM/25 | 544,0 | 295 | 41 | 46 | 1.850,0 | 364 | 421 | |||||||
1 x 240 RM/25 | 706,0 | 295 | 43 | 48 | 2.050,0 | 422 | 496 | |||||||
1 x 300 RM/25 | 882,0 | 295 | 46 | 51 | 2.350,0 | 476 | 568 | |||||||
1 x 400 RM/35 | 1.176,0 | 410 | 49 | 54 | 2.800,0 | 541 | 650 |