APPLICATION
Firetec single core fire resistant cable is designed to be installed in metal conduit. For use in alarm and emergency lighting circuits for new installations or upgrading existing conduit systems to fire performance standards. Elastomeric insulation gives high mechanical strength, excellent flexibility and resistance to abrasion.
CONSTRUCTION
Conductor
Class 2 stranded annealed copper conductor according to BS EN 60228 (previously BS 6360)
Separator
Mica/glass fire barrier tape
Insulation
LSZH (Low Smoke Zero Halogen)
Inner Sheath
Halogen free compound
Concentric Conductor
Copper wires with a counter helix of copper tape
Outer Sheath
Halogen free polymer Type HM 4 according to VDE 0207
STANDARDS
Generally to BS EN 50525-3-41, BS 6387 C, W, Z, BS EN/IEC 60331-21, BS EN/IEC 60228, BS EN 50200 PH120, BS 8434-2, BS EN/IEC 60754,
BS EN/IEC 61034, BS EN/IEC 60332
We supply LPCB Certified products
The electrical and dimensional properties of this product are measured by the Technical and Quality Assurance department at the Cables laboratory. Cable performance in respect of conductor resistance, construction quality (workmanship), dimensional consistency, and other parameters are verified to published standards and approved product drawings. Conformance to RoHS (Restriction of the use of Hazardous Substances) is determined and confirmed
CHARACTERISTICS
Voltage Rating
600/1000V
Test Voltage
4kV AC
Operating Temperature
-10°C to +90°C
Minimum Bending Radius
6 x overall diameter
Insulation Colour
Brown Black Grey Blue Red Orange Yellow
Green/Yellow