Add to Cart
Low Voltage Flame Retardant Cable Environment Friendly Copper Core BS EN 60332-3-24
APPLICATION
Safety cables are used in all locations where a high degree of protection against fire and fire-damage has to be provided for human life and equipment and are, therefore, subject to high security requirements. These cables may be used indoors and outdoors. They may not be installed directly into the ground or into water. Fire resistant to FE 180 and Circuit Integrity to E 90.
CONSTRUCTION
Conductor
Solid or stranded copper conductor
Class 1 solid copper conductor to BS EN 60228 (previously BS 6360)
Class 2 stranded copper conductor to BS EN 60228 (previously BS 6360)
Insulation
Flame protecting wrapping
Halogen free polymer Type HXI 1 according to VDE 0266
Inner Sheath
Halogen-free compound
Outer Sheath
Halogen free polymer Type HM 4 according to VDE 0207
STANDARDS
DIN VDE 0266, DIN VDE 0276-604 BS/DIN EN 60228 class 1 and 2 (construction) HD 308 S2 (core identification), DIN VDE 0472-814 DIN 4102-12, IEC 60332-3-Cat.C, BS EN 60332-3-24
We supply LPCB Certified products
The electrical and dimensional properties of this product are measured by the Technical and Quality Assurance department at the Cables laboratory. Cable performance in respect of conductor resistance, construction quality (workmanship), dimensional consistency, and other parameters are verified to published standards and approved product drawings. Conformance to RoHS (Restriction of the use of Hazardous Substances) is determined and confirmed
CHARACTERISTICS
Voltage Rating
600/1000V
Test Voltage
4000V AC
Operating Temperature
-5°C to +90°C
Operating Temperature
+250°C
Minimum Bending Radius
Single core: 12 x overall diameter
Multi-core: 15 x overall diameter
Outer Sheath Colour
Black