EPR Insulation Medium Voltage Power Cables Single Core / 3 Core XLPE Cable N2XSY
Application
For use in aerial, direct burial, cable tray, conduit, and underground duct installations as permitted by the National Electric Code. The cable is capable of operating continuously with a conductor temperature not to exceed 105C for normal operation, 140C for emergency overload conditions, and 250C for short circuit conditions. It is rated at 15,000V with 133% insulation level (ungrounded system). Maximum sidewall perssure is 1000 lbs.
Conductor
Compact stranded AA-8000 series aluminum alloy per ASTM B801 or ASTM B836 and ASTM B800 and ICEA Part 2, Section 2.1 and 2.5
Conductor Shield
Extruded semi-conducting thermoset polymeric layer over the conductor, applied in tandem and firmly bonded to the insulation
Insulation
Ethylene propylene rubber (EPR) with a nominal thickness of 0.220"
Insulation Shield
Extruded layer of semi-conducting thermosetting material. Over this layer will be applied a helically wrapped 5-mil copper tape shield with minimum 25% overlap
Jacket
Black sunlight resistant PVC per ICEA S-97-682, with average thickness in accordance to Table 7-3 of ICEA
Additional Standards
UL 1685 - 1/0 AWG and larger, UL-CT Flame Exposure Test
UL 1072 - Medium Voltage Power Cables
ICEA S-93-639
ICEA S-97-682
IEEE 1202/FT4